1000-HOUR TEST OF 30-KW BRUSHLESS GENERATOR SET
Abstract
A 30-kw diesel-engine-diven generator set that had been modified to incorporate a brushless generator design and a static-type voltage regulator was investigated. The 30-kw modified brushless generator set was found to have excellent power-generating characteristcs for 60 c operation at the 120/208 voltage connection. It completed more than 1000 hours of operation at various power factor loads, and the average voltage-droop characteristics indicate that two simiar units could be expected to operate satisfactorily in parallel. It is recommended the brshless generator set deign be in-service tested. (Author)
Document Details
- Document Type
- Technical Report
- Publication Date
- Nov 23, 1962
- Accession Number
- AD0290698
Entities
People
- R.h. Leseberg
Organizations
- Naval Facilities Engineering Service Center