Fault Carrying Capacity-Santon 200A Admiralty Type Rotary Switch
Abstract
An investigation was made into the ability of a 200A Triple Pole Santon Rotary Switch, Admiralty Type, to carry heavy fault currents until they were cleared by the overload release of a feeder breaker. The tests described in this report are of the nature of a go-no go variety, and were made with direct current. The maximum safe current was found to be of the order of 10,000A at 628v D.C.
Document Details
- Document Type
- Technical Report
- Publication Date
- Sep 25, 1964
- Accession Number
- AD0355388
Entities
People
- H. H. Button
Organizations
- Admiralty Engineering Laboratory