DISCHARGE MONITORING MEDIA AND SYSTEM OF AUTOMATIC CHARGING OF ALKALI STORAGE BATTERIES.

Abstract

The means for the monitoring of the discharging and charging of the storage batteries consists of a plug-in automatic device, the ShA-1, with a maximum current protection and a counter of ampere hours. The plug-in automatic device represents a two-chamber explosion-proof body in one of the chambers on which there is mounted a two-pole automatic unit, and in the other a counter of electrical energy. As the counter, there is used a mercury indicator of the energy received by the battery (in ampere-hours) in the charging and the amount of it leaving the battery in the discharging. The system of the automatic charging of the battery (see drawing) consists of a relay of voltage and current and a blocking relay, the two of which in the assembly with the counter of electric energy, assure the automatic cutting in on charging and cutting out on finishing the discharging.