Radiofrequency Interference/Electromagnetic Interference Measurements. Oakland Air Route Traffic Control Center.
Abstract
The report describes electromagnetic interference tests at the Oakland Air Route Traffic Control Center (ARTCC), Oakland, California. The tests included measurement of radiated and conducted emission from both the automated system and non-automated equipments, and radiated and conducted susceptibility of the automated system. Conducted and radiated electric and magnetic field emission from most of the automated system equipments exceeded the limits of MIL-STD-461A, but was not sufficiently high to adversely affect other equipment certified to MIL-STD-461A. Most of the automated system equipments met the susceptibility limits of MIL-STD-461A. Exceptions were the Plan View Display, Common Logic Unit, Tape Drive, M1 display and System Control Console. (Modified author abstract)
Document Details
- Document Type
- Technical Report
- Publication Date
- May 01, 1974
- Accession Number
- AD0779746
Entities
People
- Margaretta V. Stone