Pilot-Scale Evaluation of the Treatability of RDX/HMX Site 'X' Facility Wastewaters.
Abstract
In this program, the feasibility of treating the wastewaters from the Site 'X' RDX/HMX manufacture facilities in aerobic rotating biological contractors (RBC) was evaluated. These wastewaters contain explosives such as RDX, HMX, and TNT; formaldehyde; formic acid; acetic acid; and solvents such as cyclohexanone and acetone. A pilot scale RBC was used in this investigation. The results from the pilot scale evaluation indicate that 95-100% soluble BOD removal can be achieved and maintained at soluble BOD loading rates of <2.5 lb/1000 sq ft/day.
Document Details
- Document Type
- Technical Report
- Publication Date
- Apr 01, 1980
- Accession Number
- ADA084657
Entities
People
- Debra A. Price
- Judith F. Kitchens
- Kenneth S. Hyde
- Raymond G. Hyde
- William E. Jones Iii
Organizations
- ARCO