Investigation of Alternatives to Exothermic Welding of Copper Conductors to Ground Rods.

Abstract

Four types of conductor to ground rod attachments were subjected to accelerated corrosion exposure and subsequent low current, high current, and simulated lightning strike tests. All samples passed all tests. This testing indicates that presently imposed restrictions on use of other than exothermic bonds for below grade use are unnecessary. (Author)