Ported-Coax Interior Sensor (PINTS)
Abstract
Although the results obtained during Concept Evaluation Program (CEP) testing of PINTS at Eglin, AFB, Florida, initially failed to achieve expected levels of false alarm rate (FAR) performance, the subsequent engineering investigation testing and data analysis positively identified the source of the high FAR problem. All test results analyzed indicated the high FAR problem could have been avoided or at least minimized by using an adequate Selection, Application, and Installation Guide (SAIG). This report presents PINTS tests objectives, descriptions, results and conclusions. Also included are appendices containing reports of EG&G Energy Measurements, Inc. and the Computing Devices Company.
Document Details
- Document Type
- Technical Report
- Publication Date
- Jun 01, 1988
- Accession Number
- ADA198248