Condensation of Refrigerants on Small Tube Bundles
Abstract
The construction of an apparatus for the condensation performance testing of a horizontal bundle of four tubes with various refrigerants was completed. The apparatus was instrumented, and data reduction software was developed to provide bundle and single tube condensation data. Two tube bundles were tested, smooth copper tubes and low integral-fin copper-nickel tubes, with two refrigerants, R-114 and R-113. An enhancement ratio of about 2.0 for the overall heat transfer coefficient was demonstrated for the finned tubes over the smooth tubes. Internal contamination, possibly due to a breakdown of the refrigerant molecules when subjected to high temperatures in the boiling chamber, inhibited further meaningful data collection. Recommendations for improvement of the test apparatus are made. Condensation; Heat-transfer coefficient; Finned tubes; Enhancement ratio; Filmwise; Inundation; Tube bundle, Refrigeration systems.
Document Details
- Document Type
- Technical Report
- Publication Date
- Dec 01, 1988
- Accession Number
- ADA205219
Entities
People
- Burlin D. Mabrey
Organizations
- Naval Postgraduate School