Boiler Emission Compliance Survey, Norton AFB CA
Abstract
At the request of USAF Clinic/SGPB, Norton AFB and HQ MAC/SG PB, compliance testing (carbon monoxide and oxides of nitrogen) of emissions from three Norton AFB boilers was conducted on 17-29 April 1989. Testing was performed to determine compliance with regards to the newly adopted Rule 1146 of the South Coast Air Quality Management District. In anticipation of further regulation. particulate emissions were also determined. Results show that non of the boiler emissions meet the 40 ppm limit for oxides for nitrogen but all meet the 400 ppm limit for carbon monoxide emissions. Keywords: Compliance testing; Air pollution; Source emission testing; Stack sampling; Carbon monoxide; Oxides of nitrogen.
Document Details
- Document Type
- Technical Report
- Publication Date
- Aug 01, 1989
- Accession Number
- ADA216690
Entities
People
- Charles W. Attebery
- Ronald W. Vaughn