Analysis of the Accidential Explosion at PEPCON, Henderson, Nevada, May 4, 1988
Abstract
Several hours of fire and numerous explosions destroyed the Pacific Engineering Company plant in Henderson, Nevada, that manufactured ammonium perchlorate (AP) for rocket fuel. This incident began about 1130 PDT on May 4, 1988, with a fire in their Batch House that grew out of control and caused a first large explosion at about 1153 PDT. The final and largest explosion occurred about 1157 PDT. Damages to the surrounding community were surveyed and interpreted as airblast overpressures versus distances, which allowed an estimate of 1-kiloton nuclear free-air-burst for the equivalent explosion yield. This could be reproduced by 250-tons TNT burst on the ground surface. Weather reports were obtained from the National Weather Services which indicated somewhat enhanced airblast propagation downwind toward northerly directions and attenuated airblast propagations upwind in southerly directions. It was impossible, for lack of winds aloft information below about 500 m above ground, to determine whether there was any atmospheric acoustic airblast focusing. Several seismic recordings in Las Vegas showed the greatest ground motion resulted from the airblast wave passage, traveling at near acoustic speed. Ground wave arrival times were not sufficiently precise to allow seismic speed interpretations. Of the 4000 tons of AP apparently stored in and around the plant, it appears that about 1500 tons detonated in the largest explosion. This leads to a conclusion that the TNT airblast equivalence factor for AP is near 1/6. An independent estimate, based on analysis of more ideal close-in structural deformations, suggested an equivalence factor of 1/3.
Document Details
- Document Type
- Technical Report
- Publication Date
- Nov 01, 1988
- Accession Number
- ADA396009
Entities
People
- Jack W. Reed
Organizations
- Sandia National Laboratories